Safety Instructions
vii
Model No.
Fuse Size (Maximum A)
Circuit Breaker (Maximum A)
Type
Rating
Type
Rating
SJ700D-007H
J
20 A
-
-
SJ700D-015H
J
20 A
-
-
SJ700D-022H
J
20 A
-
-
SJ700D-037H
J
20 A
-
-
SJ700D-040H
J
20 A
-
-
SJ700D-055H
J
40 A
Inverse time
40 A
SJ700D-075H
J
40 A
Inverse time
40 A
SJ700D-110H
J
40 A
Inverse time
40 A
SJ700D-150H
J
75 A
Inverse time
75 A
SJ700D-185H
J
75 A
Inverse time
75 A
SJ700D-220H
J
75 A
Inverse time
75 A
SJ700D-300H
J
100 A
Inverse time
100 A
SJ700D-370H
J
100 A
Inverse time
100 A
SJ700D-450H
J
150 A
Inverse time
150 A
SJ700D-550H
J
150 A
Inverse time
150 A
SJ700D-750H
J
225 A
Inverse time
225 A
SJ700D-900H
J
225 A
Inverse time
225 A
SJ700D-1100H
J
300 A
Inverse time
300 A
SJ700D-1320H
J
350 A
Inverse time
350 A
SJ700D-1500H
J
350 A
Inverse time
350 A
Note) Please select an appropriate fuse or an appropriate circuit breaker for a system.
(12) “Field wiring connection must be made by a UL Listed and CN closed-loop terminal connector sized for the wire
gauge involved. Connector must be fixed using the crimp tool specified by the connector manufacturer.”
(13) “Motor over temperature protection is not provided by the drive.”
DANGER! RISQUE DE BLESSURE OU DE CHOC ELECTRIQUE
- Lire attentivement le manuel avant l’installation et suivre les instructions
- Avant d’intervenir dans le variateur, couper le circuit de puissance et attendre 10 minutes avant d’ouvrir le capot
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...