Chapter 4
Explanation of Functions
4-90
4.2.97 Sensorless vector, 0 Hz domain control
The 0Hz domain sensorless vector (SLV) control function
incorporates Hitachi’s own torque control system and enables
high-torque operation in the 0Hz range (0 to 3 Hz). This control
function is best suited for driving a lifting machine, e.g., crane or
hoist, that requires sufficient torque when starting at a low
frequency.
To use this function, specify "04" for the V/F characteristic curve
selection (A044/A244).
Before using this function, be sure to optimize constant settings
for the motor with reference to Section 4.2.91, "Motor constant
selection."
The parameters related to the 0Hz-range sensorless vector control
are as follows:
1) The Zero LV lmit for 1st/2nd motors (H060/H260) is the
parameter that specifies the output current for the
constant-current control in the 0 Hz range (about 3.0 Hz or less).
The parameter value is expressed as a ratio of the output current
to the inverter's rated current.
2) The Zero LV starting boost current (H061/H261) is the parameter to specify the current for boosting at motor
start-up with a frequency in the 0 Hz range. The parameter value is expressed as a ratio of the boost current to the
inverter's rated current. The value of the boost current is added to the current value specified by "H060/H260" only at
starting.
Item
Function code
Range of data
Description
Zero LV lmit
H060/H260
0.0 to 100.0 (%)
Current limiter for the low-speed range
Zero LV starting boost current
H061/H261
0. to 50. (%)
Quantity of boost current at starting
When using this function, observe the following precautions:
1) Be sure to use an inverter of which the capacity is one class higher than the motor to be driven.
2) If you use the inverter to drive a motor of which the capacity is two classes lower than the maximum applicable
capacity of the inverter, you may not be able to obtain adequate motor characteristics.
3) If you cannot obtain desired characteristics from the motor driven under the 0Hz-range sensorless vector control,
readjust the motor constants according to the symptom as described in the table below.
Operation
status
Symptom
Adjustment method
Adjustment item
Powering
Momentary speed
variation is negative.
Increase the motor constant R2 step by step from the set
value up to 1.2 times as high as the set value.
H021/H221/H031
Momentary speed
variation is positive.
Reduce the motor constant R2 step by step from the set
value down to 0.8 times as high as the set value.
H021/H221/H031
Regenerating
Torque is insufficient at
low frequencies (several
Hz)
Increase the motor constant R1 step by step from the set
value up to 1.2 times as high as the set value.
H020/H220/H030
Increase the motor constant I0 step by step from the set
value up to 1.2 times as high as the set value.
H023/H223/H033
Starting
The motor generates an
impact when it starts.
Reduce the motor constant J from the set value.
H024/H224/H034
Decelerating
The motor runs
unsteadily.
Reduce the speed response setting.
H005/H205
Reduce the motor constant J from the set value.
H024/H224/H034
Immediately
after
deceleration
Overcurrent or
overvoltage protection
function operates.
Reduce the motor constant I0 step by step from the set
value down to 0.8 times as high as the set value.
H023/H223/H033
Specify "00" (always on) or "01" (always off) for the AVR
function select (A081).
A081
Low-frequency
operation
Motor rotation is
inconsistent.
Increase the motor constant J from the set value.
H024/H224/H034
Note 1: Always set the carrier frequency (b083) to 2.1 kHz or more. If the carrier frequency is less than 2.1 kHz, the
inverter cannot operate the motor normally.
Note 2: Adjust the torque limit (b041 to b044) so that the value "
" calculated by the expression below does not
exceed 200%. Otherwise, the motor may be burnt out.
= "torque limit" x (inverter capacity)/(motor capacity)
(Example) When the inverter capacity is 0.75 kW and the motor capacity is 0.4 kW, the torque limit value is
calculated as follows on the assumption that the value "
" should be 200%:
Torque limit (b041 to b044) =
x (motor capacity)/(inverter capacity) = 200% x (0.4 kW)/(0.75
kW) = 106%
A001: Frequency source setting
A044/A244: V/F characteristic curve selection, 1st/2nd
motors
F001: Output frequency setting
b040: Torque limit selection
b041 to b044: Torque limit (1) to (4)
H002/H202: Motor data selection, 1st/2nd motors
H003/H203: Motor capacity, 1st/2nd motors
H004/H204: Motor poles setting, 1st/2nd motors
H005/H205: Motor speed constant, 1st/2nd motors
H020/H220: Motor constant R1, 1st/2nd motors
H021/H221: Motor constant R2, 1st/2nd motors
H022/H222: Motor constant L, 1st/2nd motors
H023/H223: Motor constant Io, 1st/2nd motors
H024/H224: Motor constant J, 1st/2nd motors
H050/H250: PI proportional gain, 1st/2nd motors
H051/H251: PI integral gain, 1st/2nd motors
H052/H252: P proportional gain setting, 1st/2nd motors
H060/H260: Zero LV lmit, 1st/2nd motors
H061/H261: Zero LV starting boost current, 1st/2nd
motors
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...