Chapter 4
Explanation of Functions
4-147
(v) List of registers (function modes)
Register No.
Function name
Function code
R/W
Monitoring and setting items
Data
resolution
1201h
Frequency source setting
A001
R/W
0 (keypad potentiometer), 1 (control circuit terminal
block), 2 (digital operator), 3 (RS485), 4 (option 1), 5
(option 2), 6 (pulse train input), 7 (easy sequence), 10
(operation function result)
-
1202h
Run command source setting
A002
R/W
1 (control circuit terminal block), 2 (digital operator), 3
(RS485), 4 (option 1), 5 (option 2)
-
1203h
1st base frequency setting
A003
R/W 30 to "1st maximum frequency"
1 [Hz]
1204h
1st maximum frequency setting
A004
R/W "1st base frequency" to 400
1 [Hz]
1205h
[AT] selection
A005
R/W
0 (switching between O and OI terminals), 1 (switching
between O and O2 terminals), 2 (switching between O
terminal and keypad potentiometer), 3 (switching
between OI terminal and keypad potentiometer), 4
(switching between O2 and keypad potentiometer)
-
1206h
[O2] selection
A006
R/W
0 (single), 1 (auxiliary frequency input via O and OI
terminals) (nonreversible), 2 (auxiliary frequency input via
O and OI terminals) (reversible), 3 (disabling O2 terminal)
-
1207h to
120Ah
(Reserved)
-
-
Inaccessible
-
120Bh
[O]-[L] input active range start
frequency
A011 (high)
R/W 0 to 40000
0.01 [Hz]
120Ch
A011 (low)
120Dh
[O]-[L] input active range end
frequency
A012 (high)
R/W 0 to 40000
0.01 [Hz]
120Eh
A012 (low)
120Fh
[O]-[L] input active range start
voltage
A013
R/W 0 to "[O]-[L] input active range end voltage"
1 [%]
1210h
[O]-[L] input active range end
voltage
A014
R/W "[O]-[L] input active range start voltage" to 100
1 [%]
1211h
[O]-[L] input active range start
frequency selection
A015
R/W 0 (external start frequency), 1 (0 Hz)
-
1212h
External frequency filter time
const.
A016
R/W 1 to 30 or 31 (500 ms filter ±0.1 Hz with hysteresis)
1
1213h
Easy sequence function
selection
A017
R/W 0 (disabling), 1 (enabling)
-
1214h
(Reserved)
-
R/W Inaccessible
-
1215h
Multispeed operation selection
A019
R/W 0 (binary), 1 (bit)
-
1216h
Multispeed frequency setting
A020 (high)
R/W
0 or "start frequency" to "1st maximum frequency"
0.01 [Hz]
1217h
A020 (low)
R/W
1218h
Multispeed 1 setting
A021 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1219h
A021 (low)
R/W
121Ah
Multispeed 2 setting
A022 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
121Bh
A022 (low)
R/W
121Ch
Multispeed 3 setting
A023 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
121Dh
A023 (low)
R/W
121Eh
Multispeed 4 setting
A024 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
121Fh
A024 (low)
R/W
1220h
Multispeed 5 setting
A025 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1221h
A025 (low)
R/W
1222h
Multispeed 6 setting
A026 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1223h
A026 (low)
R/W
1224h
Multispeed 7 setting
A027 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1225h
A027 (low)
R/W
1226h
Multispeed 8 setting
A028 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1227h
A028 (low)
R/W
1228h
Multispeed 9 setting
A029 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1229h
A029 (low)
R/W
122Ah
Multispeed 10 setting
A030 (high)
R/W 0 or "start frequency" to "maximum frequency"
0.01 [Hz]
122Bh
Multispeed 11 setting
A030 (low)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
122Ch
A031 (high)
R/W
122Dh
Multispeed 12 setting
A031 (low)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
122Eh
A032 (high)
R/W
122Fh
Multispeed 13 setting
A032 (low)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1230h
A033 (high)
R/W
1231h
Multispeed 14 setting
A033 (low)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1232h
A034 (high)
R/W
1233h
Multispeed 15 setting
A034 (low)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1234h
A035 (high)
R/W
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...