Chapter 8
List of Data Settings
8-8
Code
Function name
Monitored data or setting
Default
Memo
Change during
RUN operation
Page
FF FEF FUF
b031
≠
10 b031=10
O
th
e
rs
b078
Cumulative input power data clearance
Clearance by setting "01" and pressing the STR key
00
Allowed Allowed
4-4
b079
Cumulative input power display gain
setting
1. to 1000.
1.
Allowed Allowed
b082
Start frequency adjustment
0.10 to 9.99 (Hz)
0.50
Not
Allowed 4-42
b083
Carrier frequency setting
0.5
~
15.0(kHz) <0.5
~
10.0(kHz)> (In case of CT)
0.5
~
12.0(kHz) (In case of VT)
5.0<3.0>(CT)
3.0(VT)
Not
Not
4-43
b084
Initialization mode (parameters or trip
history)
00 (disabled), 01 (clearing the trip history), 02 (initializing the data),
03 (clearing the trip history and initializing the data), 04 (clearing the
trip history and initializing the data and EzSQ program)
00
Not
Not
4-75
b085
Country code for initialization
00 (Japan), 01 (EU), 02 (U.S.A.)
00 01 02
Not
Not
b086
Frequency scaling conversion factor
0.1 to 99.0
1.0
Allowed Allowed
4-2
b087
STOP key enable
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00
Not
Allowed
4-9
b088
Restart mode after FRS
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (starting with active matching frequency)
00
Not
Allowed 4-52
b089
Automatic carrier frequency reduction
00: invalid, 01: valid
00
Not
Not
4-44
b090
Dynamic braking usage ratio
0.0 to 100.0 (%)
0.0
Not
Allowed 4-45
b091
Stop mode selection
00 (deceleration until stop), 01 (free-run stop)
00
Not
Allowed
4-9
b092
Cooling fan control
00 (always operating the fan), 01 (operating the fan only during
inverter operation [including 5 minutes after power-on and
power-off])
00
Not
Allowed
4-45
b095
Dynamic braking control
00 (disabling), 01 (enabling [disabling while the motor is topped]),
02 (enabling [enabling also while the motor is topped])
00
Not
Allowed
b096
Dynamic braking activation level
330 to 380, 660 to 760(V)
360/720
Not
Allowed
b098
Thermistor for thermal protection
control
00 (disabling the thermistor), 01 (enabling the thermistor with PTC),
02 (enabling the thermistor with NTC)
00
Not
Allowed
4-72
b099
Thermal protection level setting
0. to 9999. (
)
3000.
Not
Allowed
Fr
ee
s
et
ti
n
g o
f V
/f
c
h
ar
ac
ter
is
ti
c
b100
Free-setting V/f frequency (1)
0. to "free-setting V/f frequency (2)" (Hz)
0.
Not
Not
4-17
b101
Free-setting V/f voltage (1)
0.0 to 800.0 (V)
0.0
Not
Not
b102
Free-setting V/f frequency (2)
"free-setting V/f frequency (1)" to "free-setting V/f frequency (3)" (Hz)
0.
Not
Not
b103
Free-setting V/f voltage (2)
0.0 to 800.0 (V)
0.0
Not
Not
b104
Free-setting V/f frequency (3)
"free-setting V/f frequency (2)" to "free-setting V/f frequency (4)" (Hz)
0.
Not
Not
b105
Free-setting V/f voltage (3)
0.0 to 800.0 (V)
0.0
Not
Not
b106
Free-setting V/f frequency (4)
"free-setting V/f frequency (3)" to "free-setting V/f frequency (5)" (Hz)
0.
Not
Not
b107
Free-setting V/f voltage (4)
0.0 to 800.0 (V)
0.0
Not
Not
b108
Free-setting V/f frequency (5)
"free-setting V/f frequency (4)" to "free-setting V/f frequency (6)" (Hz)
0.
Not
Not
b109
Free-setting V/f voltage (5)
0.0 to 800.0 (V)
0.0
Not
Not
b110
Free-setting V/f frequency (6)
"free-setting V/f frequency (5)" to "free-setting V/f frequency (7)" (Hz)
0.
Not
Not
b111
Free-setting V/f voltage (6)
0.0 to 800.0 (V)
0.0
Not
Not
b112
Free-setting V/f frequency (7)
"free-setting V/f frequency (6)" (Hz) to 400. (Hz)
0.
Not
Not
b113
Free-setting V/f voltage (7)
0.0 to 800.0 (V)
0.0
Not
Not
O
th
e
rs
b120
Brake Control Enable
00 (disabling), 01 (enabling)
00
Not
Allowed
4-81
b121
Brake Wait Time for Release
0.00 to 5.00 (s)
0.00
Not
Allowed
b122
Brake Wait Time for Acceleration
0.00
Not
Allowed
b123
Brake Wait Time for Stopping
0.00
Not
Allowed
b124
Brake Wait Time for Confirmation
0.00
Not
Allowed
b125
Brake Release Frequency Setting
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
Not
Allowed
b126
Brake Release Current Setting
0.0 to 2.00 x "rated current" <0.0 to 1.80 x "rated current">
Rated current
Not
Allowed
b127
Braking frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
Not
Allowed
Ove
rvolt
age
s
uppr
es
sion
b130
Overvoltage suppression enable
00 (disabling the restraint), 01 (controlled deceleration),
02 (enabling acceleration),. 03 (enabling acceleration)
00
Not
Allowed
4-41
b131
Overvoltage suppression level
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
380/760
Not
Allowed
b132
Acceleration and deceleration rate at
overvoltage suppression
0.10 to 30.00 (s)
1.00
Not
Allowed
b133
Overvoltage suppression propotional
gain
0.00 to 2.55
0.50
Allowed Allowed
b134
Overvoltage suppression Integral time
0.000 to 9.999 / 10.00 to 65.53 (s)
0.060
Allowed Allowed
Othe
rs
b141
Output loss detection enable
00 (disabling), 01 (enabling)
00
Not
Allowed
4-36
b142
Output loss detection sensibility
1.~100.(%)
10.
Allowed Allowed
b164
Automatic return to initial display
00 (disabling), 01 (enabling)
00
Allowed Allowed 4-78
b166
Data Read/Write select
00 (Read/Write OK), 01 (Protected)
00
Not
Allowed 4-95
b180
Initialization trigger
00 (Initialization disable), 01 (Perform initialization)
00
Not
Not
4-75
(Note)<>indicate the setting range of 75 to 150kW