Chapter 4
Explanation of Functions
4-32
(2) Curve constant (swelling degree)
Specify the swelling degree of the acceleration curve with reference to the following graphs:
The acceleration or deceleration time may be shortened midway through the acceleration or deceleration according to
the S-curve pattern.
If the LAD cancellation (LAC) function has been assigned to an intelligent input terminal and the LAC terminal is turned
on, the selected acceleration and deceleration patterns are ignored, and the output frequency is quickly adjusted to
that specified by the frequency command.
(3) Curvature of EL-S-curve pattern
When using the EL-S-curve pattern, you can set the curvatures (A150 to A153) individually for acceleration and
deceleration.
If all curvatures are set to 50%, the EL-S-curve pattern will be equivalent to the S-curve pattern.
4.2.26 Energy-saver operation
The energy-saver operation function allows you to automatically minimize the
inverter output power while the inverter is driving the motor at constant speed.
This function is suited to operating a fan, pump, or other load that has a
reduced-torque characteristic.
To use this function, specify "01" for the operation mode selection (A085).
Use the energy saving mode tuning function (A086) to adjust the response and accuracy of the energy-saver operation.
The energy-saver operation function controls the inverter operation comparatively slowly. Therefore, if a sudden
change in the load occurs (e.g., impact load is applied), the motor may stall, and, consequently, the inverter may trip
because of overcurrent.
Item
Function code
Data
Description
Operation mode selection
A085
00
Normal operation
01
Energy-saving operation
02
Fuzzy operation
Item
Function code
Data
Response
Accuracy
Energy saving mode tuning
A086
0
100
Slow
Quick
High
Low
96.9
82.4
17.6
3.1
25
50
75
10
02
10
02
99.6
93.8
35
25
50
75
10
10
02
87.5
68.4
64.6
65
35.4
0.39
25
50
75
10
02
31.6
12.5
6.25
Output frequency (Hz)
Output frequency (Hz)
Output frequency (Hz)
Target
frequency
(100%)
Target
frequency
(100%)
Target
frequency
(100%)
Acceleration time (100%) to reach the
set output frequency
Acceleration time (100%) to reach the
set output frequency
Acceleration time (100%) to reach the
set output frequency
Time
Time
Time
A085: Operation mode selection
A086: Energy saving mode tuning
Related code
100
50
Time (s)
Output frequency rate (%)
Curvature for
acceleration 2
(A151)
Curvature for
deceleration 1
(A152)
Curvature for
deceleration 2
(A153)
Curvature for acceleration 1
(A150)