Chapter 3
Operation
3-21
Operating run command
(A) A001=02: Digital operator
RUN and STOP key on the digital operator allows you to start and stop the motor respectively.
RUN: STOP:
*) Changing the rotatory direction can be done by changing the parameter F004, keypad run key routing or to exchange
any two phases of the wiring to the motor. Before wiring, you should confirm that the power supply to the inverter
has been cut off.
(B) A001=01: Control terminal
You can start and stop the motor operation via the FW terminal (forward rotation) or RV terminal (Reverse rotation).
In case of terminal FW:
Sink logic (short between P24 and PLC)
FW-CM1 short: The inverter runs the motor in the forward direction --- RUN command is active.
FW-CM1 open: The inverter decelerates and stops the motor --- RUN command is not active.
Source logic (short between CM1 and PLC)
FW-P24 short: The inverter runs the motor in the forward direction --- RUN command is active.
FW-P24 open: The inverter decelerates and stops the motor --- RUN command is not active.
RUN
STOP/
RESET
ON
Motor
Speed
Time
RUN
command
Frequency
command
Motor
speed