Chapter 4
Explanation of Functions
4-149
Register No.
Function name
Function code
R/W
Monitoring and setting items Data resolution
Data
resolution
125Fh
PID Function Enable
A071
R/W
0 (disabling), 1 (enabling), 2 (enabling inverted-data
output)
-
1260h
PID proportional gain
A072
R/W 2 to 50
0.1
1261h
PID integral time constant
A073
R/W 0 to 36000
0.1 [sec.]
1262h
PID derivative gain
A074
R/W 0 to 10000
0.01 [sec.]
1263h
PV scale conversion
A075
R/W 1 to 9999
0.01
1264h
PV source setting
A076
R/W
0 (input via OI), 1 (input via O), 2 (external communication),
3 (pulse train frequency input), 10 (operation result output)
-
1265h
Reverse PID
A077
R/W 00 (disabling), 01 (enabling)
-
1266h
PID output limiter
A078
R/W 0 to 1000
0.1 [sec.]
1267h
PID feed forward selection
A079
R/W 0 (disabled), 1(O input), 2 (OI input), 3 (O2 input)
-
1268h
(Reserved)
-
R/W Inaccessible
-
1269h
AVR function select
A081
R/W 0 (always on), 1 (always off), 2 (off during deceleration)
-
126Ah
AVR voltage select
A082
R/W
200 V class: 0 (200)/1 (215)/2 (220)/3 (230)/4 (240)
400 V class: 5 (380)/6 (400)/7 (415)/8 (440)/9 (460)/ 10 (480)
-
126Bh
(Reserved)
-
R/W Inaccessible
-
126Ch
(Reserved)
-
R/W Inaccessible
-
126Dh
Operation mode selection
A085
R/W
0 (normal operation), 1 (energy-saving operation),
2 (fuzzy operation)(Only CT)
-
126Eh
Energy saving mode tuning
A086
R/W 0 to 1000
0.1 [%]
126Fh to
1273h
(Reserved)
-
-
Inaccessible
-
1274h
Acceleration (2) time setting
A092 (high)
R/W
1 to 360000
0.01 [sec.]
1275h
A092 (low)
R/W
1276h
Deceleration (2) time setting
A093 (high)
R/W
1 to 360000
0.01 [sec.]
1277h
A093 (low)
R/W
1278h
Select method to switch to
Acc2/Dec2 profile
A094
R/W 0 (switching by 2CH terminal), 1 (switching by setting)
-
1279h
Acc1 to Acc2 frequency
transition point
A095 (high)
R/W
0 to 40000
0.01 [Hz]
127Ah
A095 (low)
R/W
127Bh
Dec1 to Dec2 frequency
transition point
A096 (high)
R/W
0 to 40000
0.01 [Hz]
127Ch
A096 (low)
R/W
127Dh
Acceleration curve selection
A097
R/W
0 (linear), 1 (S curve), 2 (U curve), 3 (inverted-U curve), 4
(EL-S curve)
-
127Eh
Deceleration curve setting
A098
R/W
0 (linear), 1 (S curve), 2 (U curve), 3 (inverted-U curve), 4
(EL-S curve)
-
127Fh
(Reserved)
-
-
Inaccessible
-
1280h
(Reserved)
-
-
Inaccessible
-
1281h
[OI]-[L] input active range
start frequency
A101 (high)
R/W
0 to 40000
0.01 [Hz]
1282h
A101 (low)
R/W
1283h
[OI]-[L] input active range
end frequency
A102 (high)
R/W
0 to 40000
0.01 [Hz]
1284h
A102 (low)
R/W
1285h
[OI]-[L] input active range
start current
A103
R/W 0 to "[OI]-[L] input active range end current"
1 [%]
1286h
[OI]-[L] input active range
end current
A104
R/W "[OI]-[L] input active range start current" to 100
1 [%]
1287h
[OI]-[L] input start frequency
enable
A105
R/W 0 (external start frequency), 1 (0 Hz)
-
1288h to
128Ch
(Reserved)
-
-
Inaccessible
-
128Dh
[O2]-[L] input active range
start frequency
A111 (high)
R/W
-40000 to 40000
0.01 [Hz]
128Eh
A111 (low)
R/W
128Fh
[O2]-[L] input active range
end frequency
A112 (high)
R/W
-40000 to 40000
0.01 [Hz]
1290h
A112 (low)
R/W
1291h
[O2]-[L] input active range
start voltage
A113
R/W -100 to "[O2]-[L] input active range end voltage"
1 [%]
1292h
[O2]-[L] input active range
end voltage
A114
R/W "[O2]-[L] input active range start voltage" to 100
1 [%]
1293h to
12A4h
(Reserved)
-
-
Inaccessible
-
12A5h
Acceleration curve constants
setting
A131
R/W 1 (smallest swelling) to 10 (largest swelling)
-
12A6h
Deceleration curve constants
setting
A132
R/W 1 (smallest swelling) to 10 (largest swelling)
-
12A7h to
12AEh
(Reserved)
-
-
Inaccessible
-
12AFh
Operation-target frequency
selection 1
A141
R/W
0 (digital operator), 1 (keypad potentiometer), 2 (input via
O), 3 (input via OI), 4 (external communication), 5 (option
1), 6 (option 2), 7 (pulse train frequency input)
-
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...