Chapter 2
Installation and Wiring
2-21
(4) Connecting a programmable controller to intelligent input terminals
When using the internal interface power supply
When using an external power supply
(Remove the jumper from the control circuit terminal block.)
Sink
lo
gic
Sou
rce
lo
gic
(5) Connecting a programmable controller to intelligent output terminals
Sink
lo
gic
Sou
rce
lo
gic
2.2.4 Wiring of the digital operator
- You can operate the inverter with not only the digital operator mounted in the inverter as standard equipment but
also an optional digital operator (OPE-S, OPE-SR, WOP).
- When you intend to remove the standard digital operator from the inverter and use it as remote equipment, request
your local Hitachi Distributor to supply a connection cable, ICS-1 (1-meter cable) or ICS-3 (3-meter cable). If you
prepare the cable by yourself, the following product is recommended:
NETSTAR-C5E PC 24AWGx4P LBH: Straight cable equipped with connector at both ends (made by Hitachi Metal, Ltd.)
- The length of the connection cable must be 3 m or less. If a cable over 3 m is used, the inverter may malfunction.
Inverter
Output module
(EH-YT**,etc.)
Jumper
S
COM
P24
PLC
CM1
FW
8
Inverter
P24
DC24V
CM1
FW
DC24V
S
COM
Output module
(EH-YTP**,etc.)
8
Inverter
Output module
(EH-YTP**,etc.)
DC24V
DC24V
COM
S
P24
PLC
CM1
FW
8
DC24V
Inverter
Output module
(EH-YT**,etc.)
S
COM
P24
PLC
CM1
FW
8
Jumper
11
12
CM2
COM
Inverter
Input module
(EH-XD**,etc.)
DC24V
Inverter
11
Input module
(EH-XD**,etc.)
12
CM2
COM
DC24V
DC24V
PLC
Summary of Contents for SJ700D-004L