Chapter 4
Explanation of Functions
4-46
4.2.39 Intelligent input terminal setting
You can assign the functions described below to intelligent input terminals
[1] to [8]. To assign the desired functions to the terminals, specify the
desired data listed in the table below for terminal settings "C001" to
"C008". For example, "C001" corresponds to intelligent input terminal [1].
You can select the a-contact or b-contact input for individual intelligent input terminals.
You can assign one function only to an intelligent input terminal. If you have attempted to assign a function to two or
more intelligent input terminals, the function is assigned to only the terminal to which you have last attempted
assignment. Function data "NO" (no assign) is assigned to other terminals, and those terminals are ineffective in terms
of functions.
After assigning the desired functions to intelligent input terminals [1] to [8], confirm that the assigned functions have
been stored on the inverter.
Data
Description
Reference item
Availability(Yes or No)
Page
CT mode VT mode
01
RV: Reverse RUN command
Operation command
Y
Y
-
02
CF1: Multispeed 1 setting (binary operation)
Multispeed operation function
Y
Y
4-48
03
CF2: Multispeed 2 setting (binary operation)
Y
Y
04
CF3: Multispeed 3 setting (binary operation)
Y
Y
05
CF4: Multispeed 4 setting (binary operation)
Y
Y
06
JG: Jogging
Jogging operation function
Y
Y
4-50
07
DB: External DC braking
DC braking (external DC braking) function
Y
Y
4-20
08
SET: Set 2nd motor data
2nd/3rd motor control function
Y
Y
4-50
09
2CH: 2-stage acceleration/deceleration
2-stage acceleration/deceleration function
Y
Y
4-30
11
FRS: Free-run stop
Free-run stop function
Y
Y
4-53
12
EXT: External trip
External trip function
Y
Y
4-58
13
USP: Unattended start protection
Unattended start protection function
Y
Y
4-57
14
CS: Commercial power source enable
Commercial power supply switching function
Y
Y
4-54
15
SFT: Software lock (control circuit terminal block) Software lock function
Y
Y
4-52
16
AT: Analog input voltage/current select
External analog input setting function
Y
Y
4-12
17
SET3: 3rd motor control
2nd/3rd motor control function
Y
Y
4-51
18
RS: Reset
Reset
Y
Y
4-55
20
STA: Starting by 3-wire input
3-wire input function
Y
Y
4-58
21
STP: Stopping by 3-wire input
Y
Y
22
F/R: Forward/reverse switching by 3-wire input
Y
Y
23
PID: PID disable
PID function
Y
Y
4-26
24
PIDC: PID reset
Y
Y
26
CAS: Control gain setting
Control gain switching function
Y
Y
4-59
27
UP: Remote control UP function
Remote control (UP/DWN) function
Y
Y
4-57
28
DWN: Remote control DOWN function
Y
Y
29
DWN: Remote control data clearing
Y
Y
31
OPE: Forcible operation
Forcible-operation function
Y
Y
4-52
32
SF1: Multispeed 1 setting (bit operation)
Multispeed operation function
Y
Y
4-48
33
SF2: Multispeed 2 setting (bit operation)
Y
Y
34
SF3: Multispeed 3 setting (bit operation)
Y
Y
35
SF4: Multispeed 4 setting (bit operation)
Y
Y
36
SF5: Multispeed 5 setting (bit operation)
Y
Y
37
SF6: Multispeed 6 setting (bit operation)
Y
Y
38
SF7: Multispeed 7 setting (bit operation)
Y
Y
39
OLR: Overload restriction selection
Overload restriction function
Y
Y
4-40
40
TL: Torque limit enable
Torque limitation function
Y
Y
4-93
41
TRQ1: Torque limit selection bit 1
Y
Y
42
TRQ2: Torque limit selection bit 2
Y
Y
43
PPI: P/PI mode selection
P/PI switching function
Y
Y
4-59
44
BOK: Braking confirmation
Brake control function
Y
N
4-82
45
ORT: Orientation
Orientation function
Y
N
4-105
46
LAC: LAD cancellation
LAD cancellation function
Y
Y
4-10
47
PCLR: Clearance of position deviation
V2 control mode selection function
Y
N
4-97
48
STAT: Pulse train position command input enable
Y
N
50
ADD: Trigger for frequency addition (A145)
Frequency addition function
Y
Y
4-14
C001 to C008: Terminal [1] to [8] functions
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...