Safety Instructions
vi
(11)
Distribution fuse / circuit breaker size marking is included in the manual to indicate that the unit shall be
connected with a listed inverse time circuit breaker, rated 600 V with the current ratings as shown in the table
below:
Model No.
Fuse Size (Maximum A)
Circuit Breaker (Maximum A)
Type
Rating
Type
Rating
SJ700D-004L
J
30 A
-
-
SJ700D-007L
J
30 A
-
-
SJ700D-015L
J
30 A
-
-
SJ700D-022L
J
30 A
-
-
SJ700D-037L
J
30 A
-
-
SJ700D-050L
J
30 A
-
-
SJ700D-055L
J
100 A
Inverse time
100 A
SJ700D-075L
J
100 A
Inverse time
100 A
SJ700D-110L
J
100 A
Inverse time
100 A
SJ700D-150L
J
125 A
Inverse time
125 A
SJ700D-185L
J
125 A
Inverse time
125 A
SJ700D-220L
J
125 A
Inverse time
225 A
SJ700D-300L
J
225 A
Inverse time
225 A
SJ700D-370L
J
225 A
Inverse time
225 A
SJ700D-450L
J
250 A
Inverse time
250 A
SJ700D-550L
J
300 A
Inverse time
300 A
Model No.
Required Torque (N.m)
Wire Range (AWG)
SJ700D-007H
1.8
14(Stranded only)
SJ700D-015H
1.8
14(Stranded only)
SJ700D-022H
1.8
14(Stranded only)
SJ700D-037H
1.8
14(Stranded only)
SJ700D-040H
1.8
14(Stranded only)
SJ700D-055H
4.0
12
SJ700D-075H
4.0
10
SJ700D-110H
4.0
8
SJ700D-150H
4.9
6
SJ700D-185H
4.9
6
SJ700D-220H
4.9
6 or 4
SJ700D-300H
4.9
3
SJ700D-370H
20.0
1
SJ700D-450H
20.0
1
SJ700D-550H
20.0
2/0
SJ700D-750H
20.0
Parallel of 1/0
SJ700D-900H
20.0
Parallel of 1/0
SJ700D-1100H
35.0
Parallel of 3/0
SJ700D-1320H
35.0
Parallel of 3/0
SJ700D-1500H
35.0
Parallel of 3/0
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...