Chapter 4
Explanation of Functions
4-125
(x) 09 command: This command checks whether set data can be stored in the EEPROM in the inverter.
- Transmission frame
Frame format
STX
Station No.
Command
BCC
CR
Description
Data size
Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32
Command
Command to be transmitted
2 bytes
09
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data." See
Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
- Response frame
Frame format
STX
Station No.
ACK
Data
BCC
CR
Description
Data size
Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32
ACK
Control code (acknowledgement)
1 byte
ACK (0x06)
Data
Data
2 bytes
"01" (enabling data storage)
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data." See
Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
Negative response: See Item (4)-(ii) of this section.
(xi) 0A command: This command stores set data in the EEPROM in the inverter.
- Transmission frame
Frame format
STX
Station No.
Command
BCC
CR
Description
Data size
Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32
Command
Command to be transmitted
2 bytes
0A
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data." See
Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.