4.4.2 Communication in Modbus-RTU mode
(1) Communication protocol
The communication between the inverter (slave) and external control system (master) is based on the following
protocol:
(i) : Query frame that is sent from the external control system to the inverter
(ii) : Response frame that is sent from the inverter to the external control system
(iii) : Communication trip limit time (C077)
If the inverter cannot complete the reception of a query from the master system (external control system) within
the communication trip limit time, after having sent a response to the preceding query, the inverter enters the
status in which to receive the query from the beginning. Subsequently, the inverter returns no response to the
master system.
After reception timeout occurs, the inverter operates according to the setting of the selection of operation after
communication error (C076). For details, see the table below. Monitoring of reception timeout begins when the
first communication is performed after the inverter power has been turned on or the inverter has been reset.
Reception timeout is monitored only when the inverter communicates with the master system.
Item
Function code
Range of data
Description
Selection of operation after
communication error
C076
00: Tripping
The inverter trips (E41) after reception timeout.
01: Tripping after
stopping the motor
The inverter decelerates and stops the motor,
and then trips (E41) after reception timeout.
02: Ignoring the errors
The inverter ignores the error without tripping
and alarm output.
03: Stopping the motor
after free-running (FRS)
The inverter stops the motor after free-running
without tripping and alarm output after
reception timeout.
04: Decelerating and
stopping the motor
The inverter decelerates and stops the motor
without tripping and alarm output after
reception timeout.
Communication trip limit
time setting
C077
0.00 to 99.99 (s)
Limit time to determine the reception timeout
Communication wait time
C078
0. to 1000. (ms)
Time to wait until the inverter starts sending a
response after reception of a query (excluding
the silent interval)
The inverter sends a response (frame (ii)) always after receiving a query (frame (i)). The inverter does not actively
output any frame to the external control system.
(ii)
(i)
(i)
External control system
Inverter
Waiting time (silent in
communication wait time [C078])
(iii) Communication trip limit time (C077)
(If reception timeout occurs, the inverter will
operate according to the setting of the operation
selection after communication error [C076].)
Time