Chapter 4
Explanation of Functions
4-148
Register No.
Function name
Function code
R/W
Monitoring and setting items Data resolution
Data
resolution
1236h
(Reserved)
-
-
Inaccessible
-
1237h
(Reserved)
-
-
Inaccessible
-
1238h
Jog frequency setting
A038
R/W "Start frequency" to 999
0.01 [Hz]
1239h
Jog stop mode
A039
R/W
0 (free-running after jogging stops [disabled during
operation])
1 (deceleration and stop after jogging stops [disabled
during operation])
2 (DC braking after jogging stops [disabled during
operation])
3 (free-running after jogging stops [enabled during
operation])
4 (deceleration and stop after jogging stops [enabled
during operation])
5 (DC braking after jogging stops [enabled during
operation])
-
123Ah
(Reserved)
-
-
-
123Bh
Torque boost method selection
A041
R/W 0 (manual torque boost), 1 (automatic torque boost)
-
123Ch
Manual torque boost value
A042
R/W 0 to 200
0.1 [%]
123Dh
Manual torque boost frequency
adjustment
A043
R/W 0 to 500
0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044
R/W
0 (VC), 1 (VP), 2 (free V/f), 3 (sensorless vector control),
4 (0Hz-range sensorless vector)(only CT),
5 (vector with sensor)(only CT)
-
123Fh
V/f gain setting
A045
R/W 20 to 100
1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046
R/W 0 to 255
1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047
R/W 0 to 255
1 [%]
1242h
to1244h
(Reserved)
-
-
Inaccessible
-
1245h
DC braking enable
A051
R/W 0 (disabling), 1 (enabling), 2 (set frequency only)
-
1246h
DC braking frequency setting
A052
R/W 0 to 40000
0.01 [Hz]
1247h
DC braking wait time
A053
R/W 0 to 50
0.1 [sec.]
1248h
DC braking force during
deceleration
A054
R/W 0 to 100 <0 to 80>(CT),0 to 70 <0 to 50>(VT)
1 [%]
1249h
DC braking time for
deceleration
A055
R/W 0 to 600
0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056
R/W 0 (edge operation), 1 (level operation)
-
124Bh
DC braking force for starting
A057
R/W 0 to 100 <0 to 80>(CT),0 to 70 <0 to 50>(VT)
1 [%]
124Ch
DC braking time for starting
A058
R/W 0 to 600
0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059
R/W 5 to 150 <5 to 100>(CT),5 to 120 <5 to 80>(VT)
0.1 [kHz]
124Eh
(Reserved)
-
-
Inaccessible
-
124Fh
1st frequency upper limit
setting
A061 (high)
R/W 0 or "1st frequency lower limit setting" to "1st maximum
frequency"
0.01 [Hz]
1250h
A061 (low)
R/W
1251h
1st frequency lower limit
setting
A062 (high)
R/W
0 or “Start frequency” to "1st upper limit setting"
0.01 [Hz]
1252h
A062 (low)
R/W
1253h
Jump (center) frequency setting
1
A063 (high)
R/W
0 to 40000
0.01 [Hz]
1254h
A063 (low)
R/W
1255h
Jump (hysteresis) frequency
width setting 1
A064
R/W 0 to 1000
0.01 [Hz]
1256h
Jump (center) frequency setting
2
A065 (high)
R/W
0 to 40000
0.01 [Hz]
1257h
A065 (low)
R/W
1258h
Jump (hysteresis) frequency
width setting 2
A066
R/W 0 to 1000
0.01 [Hz]
1259h
Jump (center) frequency setting
3
A067 (high)
R/W
0 to 40000
0.01 [Hz]
125Ah
A067 (low)
R/W
125Bh
Jump (hysteresis) frequency
width setting 3
A068
R/W 0 to 1000
0.01 [Hz]
125Ch
Acceleration stop frequency
setting
A069 (high)
R/W
0 to 40000
0.01 [Hz]
125Dh
A069 (low)
R/W
125Eh
Acceleration stop time
frequency setting
A070
R/W 0 to 600
0.1[s]
(Note) <>indicate the setting range of 75 to 150kW