Chapter 4
Explanation of Functions
4-153
Register No.
Function name
Function code R/W
Monitoring and setting items Data resolution
Data
resolution
1354h
(Reserved)
-
-
Inaccessible
-
1355h
Start frequency adjustment
b082
R/W 10 to 999
0.01 [Hz]
1356h
Carrier frequency setting
b083
R/W 5 to 150 <5 to 120>(CT), 5 to 120 <5 to 80>(VT)
0.1 [kHz]
1357h
Initialization mode (parameters or
trip history)
b084
R/W
00 (disabled), 01 (clearing the trip history), 02 (initializing the
data),03 (clearing the trip history and initializing the data),
04 (clearing the trip history and initializing the data and EzSQ
program)
-
1358h
Country code for initialization
b085
R/W 0 (Japan), 1 (EU), 2 (U.S.A.)
-
1359h
Frequency scaling conversion factor
b086
R/W 1 to 999
0.1
135Ah
STOP key enable
b087
R/W 0 (enabling), 1 (disabling), 2 (disabling only stop)
-
135Bh
Restart mode after FRS
b088
R/W
0 (starting with 0 Hz), 1 (starting with matching
frequency), 2 (starting with active matching frequency)
-
135Ch
(Reserved)
-
-
Inaccessible
-
135Dh
Dynamic braking usage ratio
b090
R/W 0 to 1000
0.1 [%]
135Eh
Stop mode selection
b091
R/W 0 (deceleration until stop), 1 (free-run stop)
-
135Fh
Cooling fan control
b092
R/W
0 (always operating the fan), 1 (operating the fan only
during inverter operation [including 5 minutes after
power-on and power-off])
-
1360h
(Reserved)
-
-
Inaccessible
-
1361h
(Reserved)
-
-
Inaccessible
-
1362h
Dynamic braking control
b095
R/W
0 (disabling), 1 (enabling [disabling while the motor is
stopped]), 2 (enabling [enabling also while the motor is
stopped])
-
1363h
Dynamic braking activation level
b096
R/W 330 to 380, 660 to 760
1. [V]
1364h
(Reserved)
-
-
Inaccessible
-
1365h
Thermistor for thermal protection
control
b098
R/W
0 (disabling the thermistor), 1 (enabling the thermistor
with PTC), 2 (enabling the thermistor with NTC)
-
1366h
Thermal protection level setting
b099
R/W 0. to 9999.
1. [Ω]
1367h
Free-setting V/f frequency (1)
b100
R/W 0. to "free-setting V/f frequency (2)"
1 [Hz]
1368h
Free-setting V/f voltage (1)
b101
R/W 0. to 8000
0.1 [V]
1369h
Free-setting V/f frequency (2)
b102
R/W 0. to "free-setting V/f frequency (3)"
1 [Hz]
136Ah
Free-setting V/f voltage (2)
b103
R/W 0. to 8000
0.1 [V]
136Bh
Free-setting V/f frequency (3)
b104
R/W 0. to "free-setting V/f frequency (4)"
1 [Hz]
136Ch
Free-setting V/f voltage (3)
b105
R/W 0. to 8000
0.1 [V]
136Dh
Free-setting V/f frequency (4)
b106
R/W 0. to "free-setting V/f frequency (5)"
1 [Hz]
136Eh
Free-setting V/f voltage (4)
b107
R/W 0. to 8000
0.1 [V]
136Fh
Free-setting V/f frequency (5)
b108
R/W 0. to "free-setting V/f frequency (6)"
1 [Hz]
1370h
Free-setting V/f voltage (5)
b109
R/W 0. to 8000
0.1 [V]
1371h
Free-setting V/f frequency (6)
b110
R/W 0. to "free-setting V/f frequency (7)"
1 [Hz]
1372h
Free-setting V/f voltage (6)
b111
R/W 0. to 8000
0.1 [V]
1373h
Free-setting V/f frequency (7)
b112
R/W 0. to 400.
1 [Hz]
1374h
Free-setting V/f voltage (7)
b113
R/W 0. to 8000
0.1 [V]
1375h to
137Ah
(Reserved)
-
-
Inaccessible
-
137Bh
Brake Control Enable
b120
R/W 0 (disabling), 1 (enabling) (Only CT)
-
137Ch
Brake Wait Time for Release
b121
R/W 0 to 500
0.01 [sec.]
137Dh
Brake Wait Time for Acceleration
b122
R/W 0 to 500
0.01 [sec.]
137Eh
Brake Wait Time for Stopping
b123
R/W 0 to 500
0.01 [sec.]
137Fh
Brake Wait Time for Confirmation
b124
R/W 0 to 500
0.01 [sec.]
1380h
Brake Release Frequency Setting
b125
R/W 0 to 40000
0.01 [Hz]
1381h
Brake Release Current Setting
b126
R/W 0 to 2000 <0 to 1800>
0.1 [%]
1382h
Braking frequency
b127
R/W 0 to 40000
0.01 [Hz]
1383h
(Reserved)
-
-
Inaccessible
-
1384h
(Reserved)
-
-
Inaccessible
-
1385h
Overvoltage suppression enable
b130
R/W
0 (disabling), 1 (enabling), 2 (enabling with
acceleration), 3(enabling with acceleration during
constant speed and deceleration)
-
1386h
Overvoltage suppression level
b131
R/W
200 V class: 330 to 390 (V)
400 V class: 660 to 780 (V)
1 [V]
1387h
Acceleration and deceleration rate
at overvoltage suppression
b132
R/W 10 to 3000
0.01 [sec.]
1388h
Overvoltage suppression
propotional gain
b133
R/W 0 to 255
0.01
1389h
Overvoltage suppression Integral
time
b134
R/W 0 to 65535
0.001 [sec.]
138Ah to
138Fh
(Reserved)
-
-
Inaccessible
-
(Note) <>indicate the setting range of 75 to 150kW