![GE Grid Solutions F60 Instruction Manual Download Page 265](http://html.mh-extra.com/html/ge-grid-solutions/f60/f60_instruction-manual_571876265.webp)
GE Multilin
F60 Feeder Protection System
5-127
5 SETTINGS
5.4 SYSTEM SETUP
5
b) BASIC CONFIGURATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
BASIC CONFIGURATION
PMU1
PMU 1 BASIC
CONFIGURATION
PMU 1
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 IDCODE:
1
Range: 1 to 65534 in steps of 1
MESSAGE
PMU 1 STN:
GE-UR-PMU
Range: 32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
MESSAGE
PMU 1 SIGNAL SOURCE:
SRC 1
Range: Available signal sources
MESSAGE
PMU 1 CLASS:
CLASS M
Range: None, CLASS M, CLASS P
MESSAGE
PMU 1 FORMAT:
Integer
Range: Integer, Floating-point
MESSAGE
PMU 1 STYLE:
Polar
Range: Polar, Rectangular
MESSAGE
PMU 1 RATE:
10/sec
Range:1/sec, 2/sec, 4/sec, 5/sec, 10/sec, 12/sec, 15/sec,
20/sec, 25/sec, 30/sec, 50/sec, 60/sec, 100/sec, 120/sec
MESSAGE
PMU 1 PHS-1:
Off
Range: Available synchrophasor values
↓
MESSAGE
PMU 1 PHS-14:
Off
Range: Available synchrophasor values
MESSAGE
PMU 1 PHS-1
NAME: GE-UR-PMU-PHS-1
Range: 16 -character ASCII string
↓
MESSAGE
PMU 1 PHS-14:
NAME: GE-UR-PMU-PHS-14
Range: 16 -character ASCII string
MESSAGE
PMU 1 A-CH-1:
Off
Range: Available FlexAnalog values
↓
MESSAGE
PMU 1 A-CH-16 (16):
Off
Range: Available FlexAnalog values
MESSAGE
PMU 1 A-CH-1:
NAME: AnalogChannel1
Range: 16 -character ASCII string
↓
MESSAGE
PMU 1 A-CH-16 (16):
NAME: AnalogChannel16
Range: 16 -character ASCII string
MESSAGE
PMU 1 D-CH-1:
Off
Range: Available FlexLogic operands
↓
MESSAGE
PMU 1 D-CH-16:
Off
Range: FlexLogic operand
Summary of Contents for F60
Page 10: ...x F60 Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 138: ...4 28 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 454: ...5 316 F60 Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 500: ...7 14 F60 Feeder Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 508: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 522: ...10 12 F60 Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 660: ...B 116 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 706: ...E 10 F60 Feeder Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 718: ...F 12 F60 Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 728: ...H 8 F60 Feeder Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 730: ...H 10 F60 Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...