100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 392
B1.6.3 Serial 1/Serial 2
Touching one of these keys performs a loopback test on the relevant Serial
port. In order for the test to be successful, a 9-way D-type socket, wired as in
fi gure B1.6.3, must be fi tted to the relevant serial port at the rear of the re-
corder. If wired as shown, the socket is suitable for testing with both EIA232
and EIA485 communications standards. The test will result in the legend 'S1(2)
Passed' or 'S1(2) Failed' replacing 'Serial 1' or 'Serial 2' on the appropriate key.
If the Serial Comms option is not fi tted, pressing either key returns a 'Failed'
message.
Figure B1.6.6 Relay board test display
EVENT INPUTS
If event input boards are fi tted, touching the option board key calls a display showing input status (1 = ac-
tive; 0 = not active). Changes in input status can be displayed by operating the 'Update' key.
B1.6.7 Input boards
This shows how many input boards are fi tted.
Main Menu
RELAY TESTS
1 (Energised)
2 (De-Energised)
3 (De-Energised)
4 (De-Energised)
Exercise relays by
touching keys.
Relay 4 greyed-out
for 3-relay boards.
Return to previous
menu level
Figure B1.6.3
Loop back test wiring
B1.6.4 Battery
This area, normally green, fl ashes red/white when the battery needs to be replaced (section B2). Battery
status is checked once every 15 minutes.
B1.6.5 Lockable
The lockable fl ap display is green if the lockable fl ap is fi tted, or fl ashes red/white if the option is not fi t-
ted.
B1.6.6 Option boards
This shows which option boards are fi tted where as viewed from the rear of the recorder.
RELAY OUTPUT BOARDS
If relay output boards are fi tted, the associated relays can be tested, by touching the Option board key,
then touching the relevant relay key to energise/de-energise the relay. Figure B1.6.6 shows a typical
display.
6
9
2
3
7
8
1
5
9-way D-type socket
(solder bucket side)
Short pin 1 to pin 7; pin 2 to pin 3;
and pin 6 to pin 8