100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
User Guide
Page 193
HA028910
Issue 13 Sep 16
4.3.21 ETHERNET/IP OPTION (Cont.)
CREATING A NETWORK SCANNER
1. In the left pane tree-view of the RSLogix 5000 window, right click on the EtherNet symbol and select
‘New Module...’ from the menu (fi gure 4.3.21l).
2. Expand the communications list (click on the + symbol) (fi gure 4.3.21m)
Figure 4.3.21l Right click on the EtherNet
symbol
Figure 4.3.21m The communications list
(unexpanded)
Figure 4.3.21n ‘Select Generic EtherNet Module’
Figure 4.3.21p Enter parameters
3. Using the scroll bar as necessary, click on the ‘Generic EtherNet Module’ item (fi gure 4.3.21n) and
click on ‘OK’ (or double click on the selected item).
4. In the Parameters page that appears (fi gure 4.3.21p), enter a name for the module, and set the follow-
ing values:
Comm Format: Data - INT
Address/Host name: The IP address of the recorder (from Operator/Network/Address menu)
Input: 100; size: 200
Output: 112; size: 200
Confi guration: 1; size 0
5. Tick (click on) the ‘Open Module Properties’ checkbox if it is not already ticked.
6. Click on ‘OK”