100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 285
Byte 0
Transaction
identifier
Transaction
identifier
Protocol
identifier
Protocol
identifier
Byte 1
Byte 2
Byte 3
Byte 4
Number of
bytes fol-
lowing (hex)
Byte 5
Always 00
Byte 6
Recorder
Modbus
address
Byte 7
MODBUS
function
code (hex)
00
00
00
00
00
13
01
Byte 8
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Byte 14
Byte 15
Byte 16
Byte 17
Byte 18
Byte 19
Byte 20
Byte 21
Byte 22
Byte 23
10
CC
Start
address
high
Start
address low
No. of regis-
ters high
No. of reg-
isters low
Byte count
30
ASCII
E (Hex)
45
Null
Password
High
Byte
0C
00
06
ASCII
n (Hex)
6E
ASCII
g (Hex)
67
ASCII
i (Hex)
69
ASCII
n (Hex)
6E
ASCII
e (Hex)
65
ASCII
e (Hex)
65
ASCII
r (Hex)
72
00
HH
User name (as configured in instrument. Must be followed by null character (Hex 00)
Byte 24
Null
00
Password
Low
Byte
HH
HH
Null character inserted only, if
otherwise, the Byte count in
Byte 12 would be Odd.
Byte 6
Slave
identifier
MODBUS
function
code (hex)
00
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
10
CC
Start
address
high
Start
address low
No. of regis-
ters high
No. of reg-
isters low
30
00
06
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Byte 14
Byte 15
Byte 16
Byte 17
Byte 18
Byte 19
Byte 20
Byte count
(excluding
CRC)
ASCII
E (Hex)
45
0C
ASCII
n (Hex)
6E
ASCII
g (Hex)
67
ASCII
i (Hex)
69
ASCII
n (Hex)
6E
Null
Password
High
Byte
ASCII
e (Hex)
65
ASCII
e (Hex)
65
ASCII
r (Hex)
72
00
HH
Null
00
Password
Low
Byte
HH
HH
Null character inserted only if
without it, the Byte count in
Byte 6 would be Odd.
CRC low
Byte
HH
HH
CRC high
Byte
8.2.4 SECURITY (Cont.)
TO SEND A LOGIN REQUEST
Request
Figure 8.2.4a shows data transmission sequence for sending a login request to a recorder with Modbus
address 1, using the Ethernet network connection. Figure 8.2.4b is the same message for use with serial
communications.
Figure 8.2.4a Login request via Ethernet (Modbus TCP)
Figure 8.2.4b Login Request using a serial transmission line.
Notes:
1 The high and low password bytes are entered using the result of the encryption program
above. If the password is blank, both High and Low Bytes must be 00 (null).
2 For successful login, the ‘Connect from remote’ item must be enabled (ref. ‘
Access levels
in sec-
tion 4.4.1).