100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
User Guide
Page 63
HA028910
Issue 13 Sep 16
4.3.1 Instrument confi guration
%
%
Minutes
s
= Disabled
0
0
Instrument Name
Instrument
Normal Display
100
Saver Display
50
Save After
30
Modbus Address
1
Modbus Security Disabled
Comms Channel Timeout
0
Preset Hour
12
Preset Minute
0
Disable Warning Dialogs
Show Operator Notes List
00:0A:8D:00:20:A0
MAC Address
Operator Note 1
Operator Note 12
Apply
Discard
These fields appear
only if 'Show Operator
Notes List' is enabled
AM Shift started
Figure 4.3.1 Instrument Confi guration menu
INSTRUMENT NAME
Allows the entry of an alphanumeric name for the recorder, up to 20 characters long. See
section 3.3.1
for text entry techniques.
NORMAL/ SAVER DISPLAY
Allows ‘normal’ and ‘saver’ display brightnesses to be defi ned. Defaults are Normal = 100%; Saver = 50%
SAVE AFTER
The number of minutes (between 1 and 99 inclusive), which are to elapse after a screen operation, before
the screen brightness changes from ‘normal’ to ‘saver’. Default is 30 minutes.
MODBUS ADDRESS
Allows a Modbus address between 1 and 247 to be set up, for use when the instrument is acting as a
Modbus slave.
MODBUS SECURITY DISABLED
When using MODBUS, it is possible, by ‘checking’ this fi eld to allow a host computer to access the record-
er without its fi rst having to supply a valid User name and Password. This box must be checked if this unit
is acting as a Modbus slave in order for the unit to be detected. Once communications have been es-
tablished, Modbus security can be enabled, providing that the Slave’s Remote user name and password
have been entered at the Master. See also
section 8.2.4
.
COMMS CHANNEL TIMEOUT
Allows a number of seconds (between 1 and 999) to be entered. If none of the channels set to ‘Comms’ is
communicated with, within this period, an event source (Comms channel timeout) is set, and remains set
until the next communication. An entry of 0 disables the time out.