100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 206
4.4.2 MANAGEMENT (Cont.)
CONFIGURABLE PARAMETERS (Cont.)
Require Authorization
This fi eld appears only if ‘Require Signing’ is enabled. If Require Authorization is
enabled, then changes to the recorder operation, confi guration (or any other item
included in the history fi le) can be made only by those users whose ‘Can Authorize’
permission is enabled in the ‘Access’ menu described in
section 4.4.1
above. When
‘Apply’ is attempted, a ‘signature’ page (fi gure 4.4.2b) appears which requires the
entry of the correct password for the selected user, and a note which would normally
be used to give the reason for the change.
Note: If neither ‘Require Signing’ nor ‘Require Authorization’ is enabled, then any user can make
changes to the recorder operation, confi guration etc. and the ‘signature’ page does not appear.
Figure 4.4.2b Signature page
Enable Audit trail For either Auditor option, if this fi eld is enabled, then all changes to confi guration are
displayed on the ‘chart’ and become part of the history fi le for each enabled group.
The following is an example of how these changes would appear on the screen for
an imaginary set up for channel 8. ‘New T/C type chan 8’ is the note entered in the
Signature page, and ‘Kiln8 temp’ is the channel descriptor.
03/08/05 11:53:01 Con
fi
guration Revision 486,144 was 486,143
03/08/05 11:52:57 Kiln8 temp Alarm Number 1, Job Number 1 Drive Relay 1 on board 7
while Unacknowledged was No action
03/08/05 11:52:57 Kiln8 temp Alarm Number 1 Threshold 530.0
˚
C was 500
03/08/05 11:52:57 Kiln8 temp Alarm Number 1 Type Absolute Low was Absolute High
03/08/05 11:52:57 Kiln8 temp Cold Junction Type Internal was External
03/08/05 11:52:57 Kiln8 temp Scale High 1000.0
˚
C was 900.0
03/08/05 11:52:57 Kiln8 temp Scale Low 450.0
˚
C was 300.0
03/08/05 11:52:57 Kiln8 temp Lin Type Type K was Type J
03/08/05 11:52:57 Con
fi
g,Signed:Engineer,Authorized:Engineer,New T/C type chan 8
(Please see notes below)
Operator Note
Signed
Frederick Bloggs
Authorised
Engineer
Password
Appears only if 'Requires Authorising' enabled
***
******
Appears only if 'Requires Signing' enabled
Ok Cancel
Note cannot be empty.
Ok
Password
Config
Pop-up appears only if 'Ok' is
operated without an operator
note having been entered.