8.4.4 GROUP DATA (Cont.)
GROUP 2
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
Grp2 Trend type
Trend enhancements
Enum
Read only A74B (42827)
1
0 = Interpolation enabled
1 = Adaptive recording enabled
Grp2 Trend rate
Trend update rate in milliseconds
Uint32
Read only A74C (42828)
2
Grp2 Archive rate
Archive (to fl ash) rate in milliseconds
Uint 32
Read only A74E (42830)
2
Grp2 Descriptor
Group descriptor (20 characters max.)
String_20
Read only A750 (42832)
10
Spare
A75A (42842)
10
Grp2 Channels in group 16 Registers holding the group contents, as follows:
(16)
Register 1
Uint16
Read only A764 (42852)
1
Bit 0: 0 = Point 1 not in group; 1 = Point 1 is in group
Bit 1: 0 = Point 2 not in group; 1 = Point 2 is in group
Bit 2: 0 = Point 3 not in group; 1 = Point 3 is in group
Etc.
Bit 15: 0 = Point 16 not in group; 1 = Point 16 is in group
Register 2 - as register 1, but for points 17 to 32
Uint16
Read only A765 (42853)
1
Register 3 - as register 1, but for points 33 to 48
Uint16
Read only A766 (42854)
1
Register 4 - as register 1, but for points 49 to 64
Uint16
Read only A767 (42855)
1
Register 5 - as register 1, but for points 65 to 80
Uint16
Read only A768 (42856)
1
Register 6 - as register 1, but for points 81 to 96
Uint16
Read only A769 (42857)
1
Register 7 - as register 1, but for points 97 to 112
Uint16
Read only A76A(42858)
1
Register 8 - as register 1, but for points 113 to 128
Uint16
Read only A76B (42859)
1
Register 9 - as register 1, but for points 129 to 144
Uint16
Read only A76C (42860)
1
Register 10 - as register 1, but for points 145 to 160
Uint16
Read only A76D (42861)
1
Register 11 - as register 1, but for points 161 to 176
Uint16
Read only A76E (42862)
1
Register 12 - as register 1, but for points 177 to 192
Uint16
Read only A76F (42863)
1
Register 13 - as register 1, but for points 193 to 208
Uint16
Read only A770 (42864)
1
Register 14 - as register 1, but for points 209 to 224
Uint16
Read only A771 (42865)
1
Register 15 - as register 1, but for points 225 to 240
Uint16
Read only A772 (42866)
1
Register 16 - as register 1, but for points 241 to 256
Uint16
Read only A773 (42867)
1
Grp2 Text length
Identifi es the length of a text message to be read
Uint16
Read/Write A774 (42868)
1
Grp2 Text time stamp
Time stamp of the text message to be read (UTC format) Double
Read only A775 (42869)
4
Grp2 Read text
Read text string from instrument display
String_60
Read only A779 (42873)
30
Reserved
A797 (42903)
30
Grp2 Write text
Write a text string to instrument display
String_60
Write only A7B5 (42933)
30
Reserved
A7D3 (42963)
30
Grp2 Batch start
Boolean Flag. Value 0001 starts new batch
Boolean
Write only A7F1 (42993)
1
Grp2 Batch stop
Boolean Flag. Value 0001 stops current batch
Boolean
Write only A7F2 (42994)
1
Grp2 Batch running
Batch status fl ag: 1 = Running; 0 = Not running
Boolean
Read only A7F3 (42995)
1
Grp2 Text fi eld 1
Batch fi eld 1 text string (max. 60 characters)
String_60
Read/Write A7F4 (42996)
30
Reserved
A812 (43026)
30
Grp2 Text fi eld 2
Batch fi eld 2 text string (max. 60 characters)
String_60
Read/Write A830 (43056)
30
Reserved
A84E (43086)
30
Grp2 Text fi eld 3
Batch fi eld 3 text string (max. 60 characters)
String_60
Read/Write A86C (43116)
30
Reserved
A88A (43146)
30
Grp2 Text fi eld 4
Batch fi eld 4 text string (max. 60 characters)
String_60
Read/Write A8A8 (43176)
30
Reserved
A8C6 (43206)
30
Grp2 Text fi eld 5
Batch fi eld 5 text string (max. 60 characters)
String_60
Read/Write A8E4 (43236)
30
Reserved
A902 (43266)
30
Grp2 Text fi eld 6
Batch fi eld 6 text string (max. 60 characters)
String_60
Read/Write A920 (43296)
30
Reserved
A93E (43326)
30
Spare
A95C (43356)
100
See
table 8.3
for point types