100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
User Guide
Page 65
HA028910
Issue 13 Sep 16
4.3.2 Group confi guration
Note: Groups 1 to 6 is a standard recorder feature. The supply of groups seven to twelve is an
optional extra.
Group confi guration allows the user to defi ne the following:
a
Group trend speed/interval
b Group recording speed/interval
c
Group descriptor
d Group content
e Circular Trend speed and chart-full operation
f
Chart grid divisions
The production of alarm messages and the saving of group data to Flash memory, to removable memory
device and/or to remote computer (FTP transfer) can also be enabled / disabled from this menu.
Figure 4.3.2a Group confi guration menu
Grid Type
Linear
Grid Divisions - Minor
Grid Divisions - Major
5
1
Apply
Discard
Alarm Message
Recording Speed
Recording Interval
Archive to Media Enable
Archive via FTP Enable
Trend History Duration
Recording Enable
Ack Message
TurbineTempA
TurbineTempB
= Enabled
Etc.
1
1,200
mm/hr
s
List of all available points
(input channels, maths
channels, totalisers etc.).
314.36
Days
Editable only if
'Recording Enable'
is enabled.
Select None, Linear, Log or
'From Point'
Grid Type
From Point
from
Channel 3
Point Type
Totaliser
Selection
1-3,5,7,9
Enable
Disable
Grid Type
Log
Grid Decades
5
Trend Units
Descriptor
Trend Speed
Trend Interval
Group Number
Trend Type
Select
mm/hr or in/hr
mm/hr
1
1,200
mm/hr
s
Group 1
1) Group 1
Select Group
Adaptive
Circular Speed
1 week
Circular Chart Full
New Chart
Start At
Monday
Appear only if 'Circular Settings'
enabled.
Circular Settings
A/B Switching
Select
Normal or Adaptive
Not editable if 'Circular
settings' enabled
Circular Extended Backfill