100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
User Guide
Page 189
HA028910
Issue 13 Sep 16
4.3.21 ETHERNET/IP OPTION (Cont.)
DEFAULT TABLE KEY
Clicking on this key causes the relevant table to be populated with a default set of parameters.
For input tables, these parameters are: Channel.1.pv to Channel.100.pv followed by Math.1.pv to
Math.100.pv.
The output table parameters are: Channel.1.pv to Channel.100.pv followed by Math.1.pv to Math.100.pv.
SHOW ERRORS KEY
Clicking on this key causes the parameter addresses to appear after the parameter names in the input
and output tables. If a syntax or other error has been made in loading the input table, a description of
the error type appears in this view (see ‘
ERROR MESSAGES
’, above).
OUTPUT TABLE PARAMETER MODBUS ADDRESSES
In all cases, the addresses for the output parameters can be viewed by operating the ‘Show errors’ key. The ad-
dresses for channels 1 to 75 and maths 1 to 100 can be found as described in
Section 8.4.3
(Channel Runtime
data), and
section 4.3.11
(Maths channel Run-time data). Addresses for channels 76 to 100, are given below:
Channel.76.pv
Channel 76 process value
Scaled
Read only
FCBF (64703)
1
Channel.77.pv
Channel 77 process value
Scaled
Read only
FCC2 (64706)
1
Channel.78.pv
Channel 78 process value
Scaled
Read only
FCC5 (64709)
1
Channel.79.pv
Channel 79 process value
Scaled
Read only
FCC8 (64712)
1
Channel.80.pv
Channel 80 process value
Scaled
Read only
FCCB (64715)
1
Channel.81.pv
Channel 81 process value
Scaled
Read only
FCCE (64718)
1
Channel.82.pv
Channel 82 process value
Scaled
Read only
FCD1 (64721)
1
Channel.83.pv
Channel 63 process value
Scaled
Read only
FCD4 (64724)
1
Channel.84.pv
Channel 64 process value
Scaled
Read only
FCD7 (64727)
1
Channel.85.pv
Channel 65 process value
Scaled
Read only
FCDA (64730)
1
Channel.86.pv
Channel 66 process value
Scaled
Read only
FCDD (64733)
1
Channel.87.pv
Channel 67 process value
Scaled
Read only
FCE0 (64736)
1
Channel.88.pv
Channel 68 process value
Scaled
Read only
FCE3 (64739)
1
Channel.89.pv
Channel 69 process value
Scaled
Read only
FCE6 (64742)
1
Channel.90.pv
Channel 70 process value
Scaled
Read only
FCE9 (64745)
1
Channel.91.pv
Channel 71 process value
Scaled
Read only
FCEC (64748)
1
Channel.92.pv
Channel 72 process value
Scaled
Read only
FCEF (64751)
1
Channel.93.pv
Channel 73 process value
Scaled
Read only
FCF2 (64754)
1
Channel.94.pv
Channel 74 process value
Scaled
Read only
FCF5 (64757)
1
Channel.95.pv
Channel 75 process value
Scaled
Read only
FCF8 (64760)
1
Channel.96.pv
Channel 76 process value
Scaled
Read only
FCFB (64763)
1
Channel.97.pv
Channel 77 process value
Scaled
Read only
FCFE (64766)
1
Channel.98.pv
Channel 78 process value
Scaled
Read only
FD01 (64769)
1
Channel.99.pv
Channel 79 process value
Scaled
Read only
FD04 (64772)
1
Channel.100.pv
Channel 80 process value
Scaled
Read only
FD07 (64775)
1
Table 4.3.21 Parameter addresses for channels 76 to 100
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
CONFIGURING A PLC
The following instructions describe how to confi gure a PLC to communicate with a Paperless graphic
recorder. Although a specifi c PLC was used in generating these instructions, the detail should be general
enough to allow any other PLC to be used.