100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 310
8.4.4
Group data
Generally: Parameter address for group N = Parameter address for group 1 + 629(N-1) (decimal)
GROUP 1
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
Grp1 Trend type
Trend enhancements
Enum
Read only A4D6 (42198)
1
0 = Interpolation enabled
1 = Adaptive recording enabled
Grp1 Trend rate
Trend update rate in milliseconds
Uint32
Read only A4D7 (42199)
2
Grp1 Archive rate
Archive (to fl ash) rate in milliseconds
Uint 32
Read only A4D9 (42201)
2
Grp1 Descriptor
Group descriptor (20 characters max.)
String_20
Read only A4DB (42203)
10
Spare
A4E5 (42213)
10
Grp1 Channels in group 16 Registers holding the group contents, as follows:
(16)
Register 1
Uint16
Read only A4EF (42223)
1
Bit 0: 0 = Point 1 not in group; 1 = Point 1 is in group
Bit 1: 0 = Point 2 not in group; 1 = Point 2 is in group
Bit 2: 0 = Point 3 not in group; 1 = Point 3 is in group
Etc.
Bit 15: 0 = Point 16 not in group; 1 = Point 16 is in group
Register 2 - as register 1, but for points 17 to 32
Uint16
Read only A4F0 (42224)
1
Register 3 - as register 1, but for points 33 to 48
Uint16
Read only A4F1 (42225)
1
Register 4 - as register 1, but for points 49 to 64
Uint16
Read only A4F2 (42226)
1
Register 5 - as register 1, but for points 65 to 80
Uint16
Read only A4F3 (42227)
1
Register 6 - as register 1, but for points 81 to 96
Uint16
Read only A4F4 (42228)
1
Register 7 - as register 1, but for points 97 to 112
Uint16
Read only A4F5 (42229)
1
Register 8 - as register 1, but for points 113 to 128
Uint16
Read only A4F6 (42230)
1
Register 9 - as register 1, but for points 129 to 144
Uint16
Read only A4F7 (42231)
1
Register 10 - as register 1, but for points 145 to 160
Uint16
Read only A4F8 (42232)
1
Register 11 - as register 1, but for points 161 to 176
Uint16
Read only A4F9 (42233)
1
Register 12 - as register 1, but for points 177 to 192
Uint16
Read only A4FA (42234)
1
Register 13 - as register 1, but for points 193 to 208
Uint16
Read only A4FB (42235)
1
Register 14 - as register 1, but for points 209 to 224
Uint16
Read only A4FC (42236)
1
Register 15 - as register 1, but for points 225 to 240
Uint16
Read only A4FD (42237)
1
Register 16 - as register 1, but for points 241 to 256
Uint16
Read only A4FE (42238)
1
Grp1 Text length
Identifi es the length of a text message to be read
Uint16
Read/Write A4FF (42239)
1
Grp1 Text time stamp
Time stamp of the text message to be read (UTC format) Double
Read only A500 (42240)
4
Grp1 Read text
Read text string from instrument display
String_60
Read only A504 (42244)
30
Reserved
A522 (42274)
30
Grp1 Write text
Write a text string to instrument display
String_60
Write only A540 (42304)
30
Reserved
A55E (42334)
30
Grp1 Batch start
Boolean Flag. Value 0001 starts new batch
Boolean
Write only A57C (42364)
1
Grp1 Batch stop
Boolean Flag. Value 0001 stops current batch
Boolean
Write only A57D (42365)
1
Grp1 Batch running
Batch status fl ag: 1 = Running; 0 = Not running
Boolean
Read only A57E (42366)
1
Grp1 Text fi eld 1
Batch fi eld 1 text string (max. 60 characters)
String_60
Read/Write A57F (42367)
30
Reserved
A59D (42397)
30
Grp1 Text fi eld 2
Batch fi eld 2 text string (max. 60 characters)
String_60
Read/Write A5BB (42427)
30
Reserved
A5D9 (42457)
30
Grp1 Text fi eld 3
Batch fi eld 3 text string (max. 60 characters)
String_60
Read/Write A5F7 (42487)
30
Reserved
A615 (42517)
30
Grp1 Text fi eld 4
Batch fi eld 4 text string (max. 60 characters)
String_60
Read/Write A633 (42547)
30
Reserved
A651 (42577)
30
Grp1 Text fi eld 5
Batch fi eld 5 text string (max. 60 characters)
String_60
Read/Write A66F (42607)
30
Reserved
A68D (42637)
30
Grp1 Text fi eld 6
Batch fi eld 6 text string (max. 60 characters)
String_60
Read/Write A6AB (42667)
30
Reserved
A6C9 (42697)
30
Spare
A6E7 (42727)
100
See
table 8.3
for point types