100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 232
4.7 JOBS
A number of sources (e.g. channel, event, totaliser) can be set up to trigger one or more jobs. The follow-
ing description includes all possible job categories, but which jobs are available on any particular record-
er depends on the options fi tted to that recorder. Many job categories require the relevant access level
permission to be set, as described in
section 4.4.1
, above.
The type of action (continuous or ‘single-shot’), available for selection, depends on the type of trigger
source. Continuous actions are selected from: While active, While inactive or While unacknowledged.
The available single-shot actions are: On becoming active, On becoming inactive, On acknowledgement.
4.7.1 No Action
This means that no job action is confi gured for the trigger source.
4.7.2 Drive relay category
Allows a specifi c relay to be set up to change state whilst the trigger source is active, inactive or whilst it
remains unacknowledged. Relays are normally energised i.e. ‘common’ (c) is shorted to ‘normally open’
(no). When in alarm, the relay is de-energised i.e. ‘common’ (c) is shorted to ‘normally closed’ (nc). Thus,
if power is removed from the recorder, all relays automatically ‘fail safe’ to their alarm conditions. See
section 2.2.1
for details of relay output board connector location(s) and pinout.
Job Number
Relay Board
Category
Relay Number
While
1
Drive Relay
Active
Select Relay
Select 'Active', 'Inacti
or 'Unacknowledged
1
1
Figure 4.7.2 Relay job menu layout
4.7.3 Totaliser category
If the Totaliser option is fi tted (
section 4.3.12
), the following jobs become available:
Preset
Loads the selected totaliser with the value set up in ‘Preset’ in the totaliser’s confi gu-
ration menu.
Preset Group
Loads all the totalisers in the specifi ed group with their ‘Preset’ values.
Disable
Stops the specifi ed totaliser accumulating.
Disable Group
Stops all totalisers in the specifi ed group.
Note: If more than one job is set up to disable a particular totaliser, then any of these jobs going
active will disable the totaliser.
Figure 4.7.3 Totaliser job menu layout (group action)
Job Number
Action
Category
Group
On
1) Group 1
1
Totaliser
Preset Group
Acknowledgement
Select 'Preset', 'Disable',
'Preset Group' or 'Disable Group'
Select Required Group
Select 'Active', 'Inactive'