Recommended fusing is 3 A fuse.
IMPORTANT: 3 A fuse is calculated without BOUT consumption nor extension modules. Real value
of fuse depends on consumption of binary outputs and modules.
Example:
Maximal consumption of binary outputs can be 22 A
2 x 10 A on high current outputs (for 10 seconds)
2 A on all others binary outputs
4.4.4 Measurement wiring
Use 1.5 mm
2
cables for voltage connection and 2.5 mm
2
for current transformers connection. Adjust
,
Nominal Voltage Ph-N (page 179)
,
Nominal Voltage Ph-Ph (page 179)
and
by appropriate setpoints in the
Basic Settings group.
IMPORTANT: Risk of personal injury due to electric shock when manipulating voltage terminals
under voltage. Be sure the terminals are not under voltage before touching them.
Do not open the secondary circuit of current transformers when the primary circuit is closed. Open
the primary circuit first.
Current measurement wiring
The number of CT’s is automatically selected based on selected value of setpoint
[3Ph4Wire / High Leg D / 3Ph3Wire / Split Ph / Mono Ph].
Generator currents and power measurement is suppressed if current level is bellow <1 % of CT range.
To ensure proper function:
Use cables of 2.5 mm
2
Use transformers to 5 A
Connect CT according to following drawings:
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...