InteliLite Global Guide
206
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0..100 [%]
Default value
80 %
Alternative config
NO
Step
1 %
Comm object
14959
Related applications
MRS. AMF
Config level
Advanced
Setpoint visibility
Only if setpoint
is not set to
Disabled
value.
Description
This setpoint adjusts threshold level for D+ function.
D+ Treshold
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
1..255 [s]
Default value
1 s
Alternative config
NO
Step
1 s
Comm object
14960
Related applications
MRS. AMF
Config level
Advanced
Setpoint visibility
Only if setpoint
is not set to
Disabled
value.
Description
This setpoint adjusts delay for D+ function. This delay is used for:
Alarm Charging Alternator Fail.
For engine running condition - disengagement of starter
D+ Delay
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
No Protec/Wrn/Sd [-]
Default value
Wrn
Alternative config
NO
Step
[-]
Comm object
15751
Related applications
MRS. AMF
Config level
Advanced
Setpoint visibility
Only if setpoint
is not set to
Disabled
value.
Description
This setpoint adjusts type of alarm Charging Alternator Fail.
D+ Alarm Type
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...