InteliLite Global Guide
219
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Disabled / 1 .. 60 [s]
Default value
30 s
Alternative config
YES
Step
1 s
Comm object
10685
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical binary output
is configured
Description
If the controller does not see the fuel increase during fuel transfer within this time alarm
will be displayed and the
will be turned off. Alarm
will be displayed but this alarm becomes immediately inactive and it will be
possible to delete this message by the Fault reset button. If the fault is deleted the controller will initiate the
transfer again.
Transfer Wrn Delay
Subgroup: Maintenance
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
-10 000 ... 9 999 [h] / Disabled
Default value
1 000 h
Alternative config
NO
Step
1 h
Comm object
11616
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer 1 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 1
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...