InteliLite Global Guide
203
Subgroup: Stopping Timers
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 3 600 [s]
Default value
30 s
Alternative config
NO
Step
1 s
Comm object
8258
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Cooling Time
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 600 [s]
Default value
60 s
Alternative config
NO
Step
1 s
Comm object
9815
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Under normal conditions the engine must certainly stop within this period after the
has been de-energized and the
energized. The Stop Solenoid output is
deactivated 12 s after last running engine indication went off.
Image 8.7 Stop Time 1
Stop Time
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...