InteliLite Global Guide
159
Reading all binary inputs as modbus register
Table: Values
Allowed MODBUS functions: 03, 04
Register(s)
Com.Obj.
Name
Dimension
Type
Len
Dec
Min
Max
Group
01068
8235
Binary
Inputs
Binary#2
2
0
-
-
Controller I/O
Request: (Numbers in Hex)
01
03
04
2C
00
01
44
F3
Controller address
Modbus function
Register address
042C
hex
=
1068
dec
Number of registers
CRC
Response: (Numbers in Hex)
01
03
02
00
12
38
49
Controller address
Modbus function
Length of data
02
hex
= 2 bytes read
Data
0012
hex
=
00010010
bin
CRC
Binary inputs is 00010010. It means Binary input 2 and binary input 5 are active.
Note:
You can use modbus function 4 insted of 3, rest of data remain same (CRC differs).
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...