If engine will not start:
Check ground connection from pick-up to controllers, eventually disconnect ground connection to one of
them.
Note:
In some cases the controller will measure a RPM value even though the gen-set is not running: RPM is
measured from the generator voltage (Gear Teeth = 0). Controller is measuring some voltage value on input
terminals due to open fusing. If RPM > 0 the controller will be put into a Not ready state and the engine will not
be allowed to start.
4.4.6 Binary inputs
Use minimally 1 mm
2
cables for wiring of Binary inputs.
Image 4.17 Wiring binary inputs
Note:
The name and function or alarm type for each binary input have to be assigned during the configuration.