Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
FGen->RPM / 1 .. 500 [-]
Default value
120
Alternative config
NO
Step
1
Comm object
8252
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Number of teeth on the engine flywheel where the pick-up is installed. Set to zero if no pick-up is used and
the Engine speed will be counted from the generator frequency.
Note:
If no pickup is used, the D+ or W terminal should be used to prevent possible overcranking, which
can occur if at least 25% of nominal generator voltage is not present immediately after exceeding firing
speed.
Gear Teeth
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
100 .. 4 000 [RPM]
Default value
1 500 RPM
Alternative config
YES
Step
1 RPM
Comm object
8253
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note:
To lock this setpoint against editing you also have to lock setpoint
,
and
.
Nominal RPM
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...