InteliLite Global Guide
160
Reading binary inputs as coil status.
Table: Binaries
Allowed MODBUS functions: 01, 02
Addresses
Modbus Addr.
Prot. Addr.
Source
= Value
= State
C.O.#
State #
Name of Value
Name of State
Bit #
Bit Name
Activated by protection(s):
Group
00000
Value
8235
Binary Inputs
1
GCB Feedback
Controller I/O
00001
Value
8235
Binary Inputs
2
MCB Feedback
Controller I/O
00002
Value
8235
Binary Inputs
3
Emergency Stop
Controller I/O
We will read state of MCB Feedback binary input.
Request: (Numbers in Hex)
01
01
00
01
00
01
AC
0A
Controller address
Modbus function
Register address
0001
hex
=
0001
dec
Number of registers
CRC
Response: (Numbers in Hex)
01
01
01
01
90
48
Controller address
Modbus function
Length of data
01
hex
= 1 byte read
Data
01
hex
= active
CRC
The readed data is 01, it means this binary input is active.
Note:
You can use modbus function 2 insted of 1, rest of data remains same (CRC differs).
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...