InteliLite Global Guide
151
Web Server Adjustment
Click to the "Web Server settings" icon in the toolbar to display the settings page.
Select the controller language the web pages will appear in.
Select the rate of automatic refresh of the scada page.
Image 6.12 Web Server - Adjustment screen
6.2 Connection to 3rd party systems
6.2.1 SNMP
SNMP is an UDP-based client-server protocol used for providing data and events into a supervisory system
(building management system). The controller plays the role of a „SNMP Agent“ while the supervisory system
plays the role of a „SNMP Manager“.
CM-Ethernet module is required for SNMP function
Supported versions - SNMP v1 and SNMP v2c
The SNMP Agent function is to be enabled by the setpoint
in the CM-Ethernet
setpoint group. The setpoints
SNMP RD Community String (page 381)
and