InteliLite Global Guide
641
Image 9.4 Configuration of Comp Hyst block
Note:
Level On and Level Off can be constants or values from controller.
IMPORTANT: In case that values on inputs have different decimal numbers than the values
are converted and the name of block is red. It is strongly recommended to use values with
the same decimal numbers.
PLC group
Comparison of analog
inputs
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
4
Inputs
Input
Type
Negation
Range
Function
Input 1
Analog
No
Any
Compared value
Input 2
Analog
No
Same as Input 1
Comparative level
Delay
Analog
No
0.0..3000,0 [s]
Comparative delay
Outputs
Output
Type
Negation
Range
Function
Output
Binary
No
0/1
Comparator output
Description
The block works as an analog switch. It compares the input value with the comparative level. The output will
switch on if the input is equal or higher than the comparative level for time longer than the delay.
Comparator With Delay
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...