InteliLite Global Guide
156
01 – Ilegal function is returned if an incompatible type of operation is applied for a specific object, e.g. if
function 03 is applied to a binary object.
02 – illegal address is returned if the client tries to perform an operation with a object address that is not
related to any existing object or that is located inside an object which is composed by multiple addresses
(registers).
04 – device error is returned in all other errorneous situations. More detailed specification of the problem can
be consequently obtained by reading the registers 4205 – 4206.
Reserved registers
There are several registers with specific meaning. These registers are available in all controllers regardless of
the configuration.
Register
addresses
Number of
registers
Access
Data type
Meaning
4200 - 4201
2
read/write
Time
RTC Time in BCD code
4202 - 4203
2
read/write
Date
RTC Date in BCD code
4204
1
read/write
Unsigned8
Index of the language that is used for text
data provided by MODBUS (e.g. alarmlist
messages).
4205 - 4206
2
read
Unsigned32
Last application error. To be read after the
device returns the exception code 04. It
contains specific information about the error.
4207 - 4208
2
read/write
Unsigned32
Writing:command argument
Reading: command return value
4209
1
write
Unsigned16
Command code
4010
1
-
-
Not implemented
4211
1
write
Unsigned16
Password
4212 - 4213
2
read
Unsigned32
Communication status
4214
1
read
Unsigned8
Number of items in the Alarmlist
4215 - 4241
27
read
Alarm
1. record in alarm list
4242 - 4268
27
read
Alarm
2. record in alarm list
4269 - 4295
27
read
Alarm
3. record in alarm list
4296 - 4322
27
read
Alarm
4. record in alarm list
4323 - 4349
27
read
Alarm
5. record in alarm list
4350 - 4376
27
read
Alarm
6. record in alarm list
4377 - 4403
27
read
Alarm
7. record in alarm list
4404 - 4430
27
read
Alarm
8. record in alarm list
4431 - 4457
27
read
Alarm
9. record in alarm list
4458 - 4484
27
read
Alarm
10. record in alarm list
4485 - 4511
27
read
Alarm
11. record in alarm list
4512 - 4538
27
read
Alarm
12. record in alarm list
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...