InteliLite Global Guide
234
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
0,0 ..
Generator Underfrequency Wrn (page 234)
[%]
Default value
85,0 %
Alternative config
NO
Step
0,1 % of
Comm object
8298
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 underfrequency.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Generator Underfrequency BOC
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
Generator Underfrequency BOC (page 234)
..
[%]
Default value
85,0 %
Alternative config
NO
Step
0,1 % of
Comm object
9689
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 underfrequency.
Generator Underfrequency Wrn
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
0,0 .. 600,0 [s]
Default value
3,0 s
Alternative config
NO
Step
0,1 s
Comm object
8297
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Generator Overfrequency BOC (page 233)
Generator Overfrequency Wrn (page 233)
,
Generator Underfrequency Wrn (page 234)
and
Generator Underfrequency BOC (page 234)
protection.
Generator <> Frequency Delay
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...