InteliLite Global Guide
180
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
0,1 .. 500,0 [V/V]
Default value
1,0 V/V
Alternative config
NO
Step
0,1 V/V
Comm object
9579
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Generator voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
PT Ratio
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
0,1 .. 500,0 [V/V]
Default value
1,0 V/V
Alternative config
NO
Step
0,1 V/V
Comm object
9580
Related applications
AMF
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Mains voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
Vm PT Ratio
Subgroup: Frequency settings
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
8278
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Frequency 2 (page 335)
and
Nominal Frequency 3 (page 339)
.
Nominal Frequency
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...