InteliLite Global Guide
331
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
12049
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note:
This value is used when any other alternate configuration is not active.
Nominal Current 1
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
9913
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
This value is used when any other alternate configuration is not active.
Nominal Frequency 1
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
100 .. 4000 [RPM]
Default value
1 500 RPM
Alternative config
YES
Step
1 RPM
Comm object
9915
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note:
This value is used when any other alternate configuration is not active.
Nominal RPM 1
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...