InteliLite Global Guide
107
Image 5.21 Breaker fail - breaker close/open opens
When binary output breaker close/open closes there is 2 sec delay for breaker fail detection.
Image 5.22 Breaker fail - breaker close/open closes
5.5.12 Exercise timers
The exercise (general-purpose) timers in controller are intended for scheduling of any operations such as e.g.
periodic tests of the gen-set, scheduled transfer of the load to the gen-set prior to an expected disconnection of
the mains etc.
Related setpoints for timer 1 are:
Timer 1 First Occur. Date (page 305)
Timer 1 First Occur. Time (page 305)
Timer 1 Repeated Day In Week (page 309)
Timer 1 Repeat Day In Month (page 309)
Timer 1 Repeat Week In Month (page 310)