InteliLite Global Guide
119
Still engine conditions
Engine speed (RPM) <
or
Oil pressure <
Starting Oil Pressure (page 192)
or
Binary input
is in logical 1 or
Generator voltage < 50 V (any phase)
Note:
When the engine was running before and all above conditions are fulfilled, additional 2 s delay is
necessary to confirm “still engine”.
When any engine running conditions are appeared on still engine than the
is
activated with following delay:
for generator voltage from 10 V to < 50 % of nominal voltage, Wrn Stop Fail has delay 1 s
for generator voltage > 50 % of nominal voltage, Wrn Stop Fail has delay 200 ms
Oil pressure >
Starting Oil Pressure (page 192)
, Wrn Stop Fail has delay 1 s
Binary input
is in logical 0, Wrn Stop Fail has delay 1 s
for detected RPM, there is no delay.
Stop engine conditions
If no engine running conditions are validated than the controller will wait extra 12 s before leaving the Machine
state Stop and than it will release the
output.
Image 5.30 Engine stops in
When the total time of stopping will exceed setpoint
than the
and binary outputs are activated. The controller will continuously try to stop the engine.
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...