InteliLite Global Guide
570
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
116
Description
This output is to be used for control of “keyswitch” input of an ECU. If the particular ECU does not have
keyswitch or a similar input, it can be used for control of DC power for the ECU.
The output closes together with
and remains closed for the entire duration that the
engine is running. It is opened at the moment that the engine comes to a stop (i.e. together with the
).
Image 8.161 ECU Power Relay
IMPORTANT: This LBO also affects evaluation of
Sd ECU Communication Fail (page 675)
or
Wrn ECU Communication Fail (page 656)
alarms. With configured LBO ECU Power Relay,
these alarms are evaluated only when this LBO is active. Without configured LBO ECU
Power Relay, these alarm are evaluated all the time.
ECU Power Relay
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
350
Description
This output is active when the ECU sends an active “red lamp” flag, i.e. it has detected a critical malfunction
and the engine should not be operated until a service check is performed. This flag is taken from the DM1
frame on standard J1939 ECUs. Some ECUs provide this flag in their own proprietary frames and some do
not provide the flag at all.
ECU Red Lamp
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...