Subgroup: Timer 1
Setpoint group
Scheduler
Related FW
1.9.0
Range [units]
Disable / No Func / /Auto Run / Mode OFF [-]
Default value
Disable
Alternative config
NO
Step
[-]
Comm object
15358
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
It is possible to choose from following timer functions. Binary output
is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if
is configured for OFF mode and
is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Disable
The Timer is disabled.
No Func
There is no any other function, only binary output of timer is activated.
Auto Run
When this option is chosen then the binary output of timer is internally connected to the
binary input.
Mode OFF
When this option is chosen then the binary output of timer is internally connected to the
Remote OFF binary input.
Timer 1 Function
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...