InteliLite Global Guide
239
Setpoint group
Protections
Related FW
1.9.0
Range [units]
Enabled / Disabled / By LBI [-]
Default value
Enabled
Alternative config
NO
Step
[-]
Comm object
15672
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint adjusts the behavior of generator Overspeed protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoint
Disabled:
Protection is disabled.
By LBI:
Protection is enabled or disabled by the state of LBI
.
Overspeed Protection
Group: Dual Operation
Subgroup: Dual Operation
Setpoint group
Dual Operation
Related FW
1.9.0
Range [units]
0,1 .. 1000,0 [h]
Default value
10 h
Alternative config
NO
Step
0,1 h
Comm object
16039
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only if relevant module is ins conditioned by the setpoint
and
Description
This setpoint adjusts the maximal allowed difference of dual operation running hours between Master and
Slave. When difference is higher, swap of load between controllers should be done.
Running Hours Max Difference
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...