InteliLite Global Guide
530
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
63
Description
Use this input for indication whether the generator circuit breaker is open or closed.
Image 8.128 GCB Feedback 1
Image 8.129 GCB Feedback 2
Note:
InteliLite controller can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
GCB Feedback
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
219
Description
This binary input can be used to adjust home position of gen-set. In case that binary input is active, setpoints
and
are adjusted automatically from actual
coordinates from GPS signal.
Note:
Input has to be activated for at least 2 seconds.
Geo Home Position