InteliLite Global Guide
105
The control outputs must be configured and wiring of the power switches must be provided in such a way,
that the controller has full control over the breakers – i.e. the controller can open and close the breaker at any
time.
The breaker must respond within max. 5 seconds to a close and open command. Special attention should be
paid to opening of motorized circuit breakers, as it could take more than 5 seconds on some types. In such
cases it is necessary to use an undervoltage coil for fast opening.
After opening the breaker, there is internal delay for another closing of breaker. Delay is 6 seconds - 5
seconds for OFF coil and 1 second for UV coil. After these 6 seconds, breaker can be closed again. For
opening of breaker there is no delay.
Breaker control outputs
Close/Open
An output for control of a contactor. Its state represents the breaker position requested by the
controller. The breaker must react within 2 seconds to a close or open command, otherwise
an alarm is issued.
ON coil
An output giving a 2 second pulse in the moment the breaker has to be closed. The output is
intended for control of close coils of circuit breakers.
OFF coil
An output giving a pulse in the moment the breaker has to be opened. The pulse lasts until
the feedback deactivates, but at least for 2 seconds. The output is intended for control of
open coils of circuit breakers.
UV coil
The GCB UV coil output is active the whole time the gen-set is running (not in idle or cooling).
The output is deactivated for at least 2 seconds in the moment the breaker has to be
switched off. The output is intended for control of undervoltage coils of circuit breakers.
Image 5.18 Breaker control outputs
Breaker fail detection
Breaker fail detection is based on binary output breaker close/open comparing with binary input breaker
feedback.
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...