InteliLite Global Guide
574
Gas:
The output closes together with binary output
when engine RPM exceed 30 RPM (fix
value).
Image 8.164 Fuel Solenoid 3
The output opens when:
Emergency Stop comes
cooled gen-set is stopped
in pause between repeated starts
back to Logical binary outputs alphabetically
LBO: G
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
41
Description
The output controls the generator circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note:
InteliLite controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
GCB Close/Open