InteliLite Global Guide
566
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1378
Description
This output is closed, when Binary Input 5 is active and open when Binary Input 5 is inactive. When Binary
Input 5 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note:
When LBI 5 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.157 Binary Input 5 Status
BIN 5 Status
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1379
Description
This output is closed, when Binary Input 6 is active and open when Binary Input 6 is inactive. When Binary
Input 6 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note:
When LBI 6 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.158 Binary Input 6 Status
BIN 6 Status
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...