InteliLite Global Guide
89
RPM = 0 or any other shutdown
condition
off,
on
Shutdown
Start request
on
Running
Stop
RPM = 0, Oil pressure not detected,
Generator voltage < 10V, D+ not
active
Ready
If at least one of engine running
indication is detected when
elapsed.
Stop (Stop
fail)
Note:
If all generator parameters are OK and
Minimal Stabilization Time (page 200)
elapsed, indicates that
GCB is possible to close. In AUTO Mode GCB is closed in this moment automatically.
Note:
The start-up sequence can be interrupted in any time by stop request
5.5.2 Operating Modes
Selecting the operating mode is done through Left
and Right
buttons on the front panel or by changing the
setpoint (from the front panel or remotely).
Note:
If this setpoint is configured as password-protected, the correct password must be entered prior to
attempting to change the mode.
Note:
The mode cannot be changed if Access Lock input is active.
The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
If the respective input is active the controller will change the mode to the respective position according to the
active input. If multiple inputs are active, the mode will be changed according to priorities of the inputs. The
priorities match the order in the list above. If all inputs are deactivated, the mode will return to the original
position given by the setpoint.
OFF
No start of the gen-set is possible. Controller stays in Not ready status and cannot be started any way. The
buttons GCB
, Start
and Stop
including the appropriate binary inputs for external buttons are not
active.
IMPORTANT: When engine is running, it is not possible to switch gen-set to OFF mode.
MAN
The engine can be started and stopped manually using the Start
and Stop
buttons (or external buttons
wired to the appropriate binary inputs) in MAN mode. When the engine is running, GCB can be closed.
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...