InteliLite Global Guide
186
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
AUTO/ECU/INTERNAL [-]
Default value
AUTO
Alternative config
NO
Step
[-]
Comm object
13345
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint selects source of running hours
AUTO
If there is some ECU which send valid running hours, then this value is used.
Otherwise value from internal counter is used.
ECU
Running hours are taken from ECU if ECU send valid data. It is not possible to set
and reset this value in statistics.
INTERNAL
Running hours are taken from internal counter. It is possible to set and reset this value
in statistics.
Note:
It is not necessary to restart controller when this setpoint is changed. Change of this setpoint
should be applied immediately.
RunHoursSource